Diesel and gas generator set selection guide

Define the load, compare quotations on the same basis, and agree on acceptance criteria before ordering a generator set.

Máy phát khí và thiết bị phân phối
Generator set installation concept.

Four steps to specify a generator set

A 24-second silent overview with on-screen text and concept imagery. The four steps are also set out below.

1. Start with the load

  • For backup power, list the loads that must stay online, the order they can reconnect, and how long they need to run.
  • For regular operation, share the daily load profile and maintenance windows. Specify whether the set runs alone, in parallel with other sets, or with the grid.
  • For data centers, industrial sites or remote facilities, include transfer requirements, sensitive loads, and redundancy needs.

2. Check fuel and site conditions

  • For diesel, check fuel storage, replenishment, containment and operating hours.
  • For pipeline or field gas, ask the supplier to assess composition, pressure and flow at the set inlet and identify any treatment required.
  • Share altitude, temperature, dust or salt exposure, and installation footprint. Compare open, enclosed or containerized packages where appropriate, including ventilation and maintenance access.

3. Compare quotes line by line

  • Ask for the exact set, engine, alternator and controller models. Compare electrical output at the same frequency, voltage, power factor, duty rating and site conditions.
  • List what the price includes. Check controls, synchronization, transfer equipment, cooling, fuel treatment, exhaust, installation and commissioning.
  • Request the emissions and other compliance documents that cover the quoted configuration and destination. Ask for written warranty terms, service coverage at the site, and spare-parts availability.

4. Agree how acceptance will work

  • Agree on factory and site tests before purchase. Define the load steps, allowable voltage and frequency deviations, and how results will be recorded.
  • Where applicable, include transfer, synchronization, protection and alarms. Agree who provides the load bank, fuel and test instruments.
  • Request the agreed test records, wiring diagrams, operating manuals, training scope and maintenance schedule as part of handover.

What to send with an inquiry

  • Company and project location, including the destination country.
  • Required electrical output, voltage and frequency. If available, include a load profile, the largest motor or load step, and the planned operating hours.
  • Available fuel. For gas, share the available pressure range and a recent gas analysis if available.
  • Standby or regular operation, islanded or grid-tied, and any space, noise or permitting constraints.